HD194Z (E) series of power meters can measure a variety of commonly used parameters and the active/ reactive power, the greatest amount of need and have a wide range of expansion of function modules: digital communication modules, digital switching modules, electric power pulse modules, and analog pulse output module to send the quantitative, can be selected flexibly. All data are available through RS-485 communication using MODBUS protocol I read, the volume of input switches can be used to monitor the status of switches; the output switch can be remote control, the more alarm; analog variables can be output to replace the traditional transmission browser. HD194Z (E) family of network (multi-) power meter can adapt to all voltage levels and the connection mode, to meet a variety of specifications of the distribution of high and low pressure switch cabinet, focus on installation.
2. Type and meaning:
_Network_(multi-function)_Power_Meter_clip_image002_0000.jpg)
3. Performance index:
| Technical parameters |
Index |
Referenced standards |
Basic power |
GB/T13978-1992 |
Active electric power |
GB/T13850-1998£¨IEC688-1992£© |
Reactive electric power |
Reactive 1.0, other 0.5 |
Accuracy class |
Input |
applicable network |
Single phase, three phase 3 wire, three phase 4 wire |
Voltage |
Rated value |
AC 100V¡¢220V¡¢380V |
Overload |
1.2 times Successively£¬2 times/10s |
Power loss |
< 0.4VA/phase |
impedance |
¡Ý200k¦¸ |
Current |
Rated value |
AC 1A¡¢5A |
Overload |
1.2 times Successively£¬10 times/10s |
Power loss |
< 0.2VA/phase |
impedance |
¡Ü0.1¦¸ |
Frequency |
50¡À5Hz, 60¡À5Hz |
Output |
electric power pulse |
2-way electric power pulse, 4-quadrant electric power measurement |
digital communication interface |
RS485/Modbus-RTU baud rate 1200/2400/4800/9600 |
switching input |
3 to 8 pole switching input, dry contact or wet contact input |
Switching output |
2 to 4 pole relay output |
Analog output |
2 to 4 pole analog transmission output, 4~20mA/0-20mA/0-5V |
Power supply |
Voltage range |
AC, DC: 80V ~ 290V, DC 20 ~ 60V(optional) |
Power loss |
< 5VA |
Insulation resistance |
¡Ý100M¦¸ |
Power frequency withstand voltage |
2Kv/1min(AC effective value for test voltage £¬input/enclosure/power supply belong) |
Protection level of cover |
IP52 |
Mean time between failures MTBF |
¡Ý50000h |
EMC |
Electrostatic discharge test |
GB/T17626.2-1998£¨IEC61000-4-2£©class 4 |
Electrical fast transplant/burst immunity test |
GB/T17626.4-1998£¨IEC61000-4-4£©class 3 test voltage: voltage current 1kV; power: 2 kV |
Surge immunity test |
GB/T17626.5-1998£¨IEC61000-4-5£©class 4 |
Ambient condition |
Temperature |
Working: -10¡æ~+55¡æ, store: -25¡æ~+70¡æ |
Relative humidity |
¡Ü90%RH, non-condensing, non-corrosive gas site |
Altitude |
¡Ü2500m |
4. Products
9S series
Installation method: screen installation (hold size: 92¡Á92 mm)
Display
_Network_(multi-function)_Power_Meter_clip_image002_0001.jpg)
9SY: measure three phase voltage, three phase current,active power, reactive power, frequency, power factor, active energy (absorb) and reactive energy (inductive), By switching means and LCD display the above power parameters, and to perserve and display the last month, 2 month ago electric power and peak balka time-sharing power.
_Network_(multi-function)_Power_Meter_clip_image002_0002.jpg)
9S4: measure three phase voltage, three phase current, active power, reactive power, frequency, power factor, active energy (absorb) and reactive energy (inductive), By switching means and 3 row 5 digits LED, and indicator light above parameters.
_Network_(multi-function)_Power_Meter_clip_image008_0000.jpg)
9S7: measure 4-quadrant electric power: active energy (Absorption and release), reactive energy (Inductive and capacitive), adopt 2 row 6 digits LED display type, display active energy (absorb) and reactive energy (inductive), when press the switch button, the meter will display active energy (absorb) and reactive energy (inductive), and continue for some time after the return to display active power (absorb) and reactive energy (inductive).
9S9: measure 3 current and one active energy, adopt 3 row 4 digits, LED display current.
Outline dimension:
_Network_(multi-function)_Power_Meter_clip_image012_0000.jpg)
|