Conformed standards:

  • Chinese GB/T 17883-1999 Alternating current static watt-hour meters for active energy (class 0.2s and 0.5s)
  • Chinese GB/T 17215-2002 Alternating current static watt-hour meters for active energy (class 1 and 2)
  • Chinese DL/T 614-2007, GB/T 17215.301-2007 Multifunction Electricity Metering Equipment
  • Chinese DL/T 645-2007 Multi-function watt-hour meter Communication protocol.
  • International standards IEC61036-2000, IEC 60687:1992

Application£º
DTSX227¡¢DSSX227 three phase active and reactive integration energy meter is designed to suitable for the power line change. It has high precision and reliability. This meter adopts the low power, large-scale, and international advanced technology integrated circuit; also it is the SMT manufacturing process. Its features are high precision, good reliability, wide load, low power, straight error curve, strong anti-interference ability.

Specifications:

Rated voltage

3¡Á220/380V

Rated current

3¡Á1.5(6)A, 3¡Á3(6)A, 3¡Á5(20)A,
3¡Á10(40)A, 3¡Á15(60)A,
3¡Á20(80)A, 3¡Á30(100)A

Frequency

50Hz ¡À 5%

Accuracy

class 1.0 for active

Starting current

for active 0.4%Ib (class 1.0)

class 2.0 for reactive

for reactive 0.5%Ib (class 2.0)

Power Factor Range

Zero Lag ~ Zero Lead

LCD display

9-digital/2 rows, IDs

Meter constant:

-imp/kWh/kvarh (according with the tender requirements)

Accuracy of RTC

0.5 s/day

Power loss

Voltage circuit ¡Ü 2W, 10VA

Storage/Transport Temp.

-40¡æ ~ +70¡æ

Current circuit ¡Ü 2.5VA

Limited OP. Voltage

70%Un ~ 120%Un

Operating Temp.

-25¡æ ~ +55¡æ

Surge Test

6 kV

Average Relative humidity

< 75%

Impulse Test

8 Kv

Dimension

228¡Á144¡Á72mm

HV Test

4 kV

Weight

1.60 kg

Features:

  • Energy measurement function:
  1. Three phase power supply, one phase or two phases power failure, the precision of measuring is not affected.
  2. Active and reactive energy measures separately.
  • Output interface:
  1. Optocoupler isolation with active and no power pulse output interface
  • Loss of phase indicates function:
  1. DTSX227, DSSX227 electronic active and reactive integration energy meter use three luminotrons to indicate if it is lack of phase. Three luminotrons separately instead of ABC phase. If one of phase was lack, the relevant indicator will put out.
  • Communication function: Infrared and RS485 communication
    1. Current reversal
    2. Earth load
  1. Advanced anti- fraud of IC card port attack,
    1. IC card contacts shorten by metal sheet
    2. Electrical spark (like motor starter)/ ESD attack on IC card contacts;
    3. AC/DC or high frequency signal injection on IC card contacts;
    4. 400Vac attack on IC card contacts
  2. Pre-alarm when out of credit, LCD flash display, Beeping (optional)
  3. High-reliable magnetic latching relay, ON/OFF 5000 times with Imax current;
  4. Cut-off user supply for overload protection, resume after 5 minutes (programmable)
  5. Highly security transaction upon encrypted data & password mechanism